Minimum off time is measured from the last start · case 01
A compressor that ran longer than the off delay restarts immediately after stopping.
Minimum off time is measured from the last start · case 02
A compressor that ran longer than the off delay restarts immediately after stopping.
Minimum off time is measured from the last start · case 03
A compressor that ran longer than the off delay restarts immediately after stopping.
Minimum off time is measured from the last start · case 04
A compressor that ran longer than the off delay restarts immediately after stopping.
Minimum off time is measured from the last start · case 05
A compressor that ran longer than the off delay restarts immediately after stopping.
Compressor starts immediately after power is restored · case 01
All units on a feeder start together after an outage because the power-up delay is skipped.
Compressor starts immediately after power is restored · case 02
All units on a feeder start together after an outage because the power-up delay is skipped.
Compressor starts immediately after power is restored · case 03
All units on a feeder start together after an outage because the power-up delay is skipped.
Compressor starts immediately after power is restored · case 04
All units on a feeder start together after an outage because the power-up delay is skipped.
Compressor starts immediately after power is restored · case 05
All units on a feeder start together after an outage because the power-up delay is skipped.
Minimum on time is measured from the first ever start · case 01
After the first cycle the compressor may stop right after starting because its start time is stale.
Minimum on time is measured from the first ever start · case 02
After the first cycle the compressor may stop right after starting because its start time is stale.
Minimum on time is measured from the first ever start · case 03
After the first cycle the compressor may stop right after starting because its start time is stale.
Minimum on time is measured from the first ever start · case 04
After the first cycle the compressor may stop right after starting because its start time is stale.
Minimum on time is measured from the first ever start · case 05
After the first cycle the compressor may stop right after starting because its start time is stale.
Heat pump compressor lockout has no release differential · case 01
Near the balance point the compressor and auxiliary heat swap every sample as outdoor temperature jitters.
Heat pump compressor lockout has no release differential · case 02
Near the balance point the compressor and auxiliary heat swap every sample as outdoor temperature jitters.
Heat pump compressor lockout has no release differential · case 03
Near the balance point the compressor and auxiliary heat swap every sample as outdoor temperature jitters.
Heat pump compressor lockout has no release differential · case 04
Near the balance point the compressor and auxiliary heat swap every sample as outdoor temperature jitters.
Heat pump compressor lockout has no release differential · case 05
Near the balance point the compressor and auxiliary heat swap every sample as outdoor temperature jitters.
Emergency heat mode still runs the compressor · case 01
Selecting emergency heat for a failed outdoor unit keeps calling the compressor.
Emergency heat mode still runs the compressor · case 02
Selecting emergency heat for a failed outdoor unit keeps calling the compressor.
Emergency heat mode still runs the compressor · case 03
Selecting emergency heat for a failed outdoor unit keeps calling the compressor.
Emergency heat mode still runs the compressor · case 04
Selecting emergency heat for a failed outdoor unit keeps calling the compressor.
Emergency heat mode still runs the compressor · case 05
Selecting emergency heat for a failed outdoor unit keeps calling the compressor.
Aux heat lockout applies while the compressor is locked out · case 01
Inside the compressor release band there is no heat source at all.
Aux heat lockout applies while the compressor is locked out · case 02
Inside the compressor release band there is no heat source at all.
Aux heat lockout applies while the compressor is locked out · case 03
Inside the compressor release band there is no heat source at all.
Aux heat lockout applies while the compressor is locked out · case 04
Inside the compressor release band there is no heat source at all.
Aux heat lockout applies while the compressor is locked out · case 05
Inside the compressor release band there is no heat source at all.
Aux strips come on with the compressor on first-stage demand · case 01
Electric strips run alongside the heat pump for small errors, wasting energy.
Aux strips come on with the compressor on first-stage demand · case 02
Electric strips run alongside the heat pump for small errors, wasting energy.
Aux strips come on with the compressor on first-stage demand · case 03
Electric strips run alongside the heat pump for small errors, wasting energy.
Aux strips come on with the compressor on first-stage demand · case 04
Electric strips run alongside the heat pump for small errors, wasting energy.
Aux strips come on with the compressor on first-stage demand · case 05
Electric strips run alongside the heat pump for small errors, wasting energy.
Defrost timer accumulates runtime with a dry coil · case 01
The unit defrosts on schedule in dry mild weather even though the coil never got cold enough to frost.
Defrost timer accumulates runtime with a dry coil · case 02
The unit defrosts on schedule in dry mild weather even though the coil never got cold enough to frost.
Defrost timer accumulates runtime with a dry coil · case 03
The unit defrosts on schedule in dry mild weather even though the coil never got cold enough to frost.
Defrost timer accumulates runtime with a dry coil · case 04
The unit defrosts on schedule in dry mild weather even though the coil never got cold enough to frost.
Defrost timer accumulates runtime with a dry coil · case 05
The unit defrosts on schedule in dry mild weather even though the coil never got cold enough to frost.
Defrost starts in warm outdoor conditions · case 01
The heat pump runs a defrost at 55 F outdoor, dumping cold air into the house for no reason.
Defrost starts in warm outdoor conditions · case 02
The heat pump runs a defrost at 55 F outdoor, dumping cold air into the house for no reason.
Defrost starts in warm outdoor conditions · case 03
The heat pump runs a defrost at 55 F outdoor, dumping cold air into the house for no reason.
Defrost starts in warm outdoor conditions · case 04
The heat pump runs a defrost at 55 F outdoor, dumping cold air into the house for no reason.
Defrost starts in warm outdoor conditions · case 05
The heat pump runs a defrost at 55 F outdoor, dumping cold air into the house for no reason.
Defrost does not terminate at exactly 57 F coil · case 01
Defrost runs past the termination point and wastes energy.
Defrost does not terminate at exactly 57 F coil · case 02
Defrost runs past the termination point and wastes energy.
Defrost does not terminate at exactly 57 F coil · case 03
Defrost runs past the termination point and wastes energy.
Defrost does not terminate at exactly 57 F coil · case 04
Defrost runs past the termination point and wastes energy.
Defrost does not terminate at exactly 57 F coil · case 05
Defrost runs past the termination point and wastes energy.
Defrost runtime accumulator is not cleared at initiation · case 01
Defrosts repeat back to back because the accumulated runtime is still above the interval.
Defrost runtime accumulator is not cleared at initiation · case 02
Defrosts repeat back to back because the accumulated runtime is still above the interval.
Defrost runtime accumulator is not cleared at initiation · case 03
Defrosts repeat back to back because the accumulated runtime is still above the interval.
Defrost runtime accumulator is not cleared at initiation · case 04
Defrosts repeat back to back because the accumulated runtime is still above the interval.
Defrost runtime accumulator is not cleared at initiation · case 05
Defrosts repeat back to back because the accumulated runtime is still above the interval.
Defrost is still reported on the minute it terminates · case 01
Every defrost is reported one minute longer and the heating restart is delayed.
Defrost is still reported on the minute it terminates · case 02
Every defrost is reported one minute longer and the heating restart is delayed.
Defrost is still reported on the minute it terminates · case 03
Every defrost is reported one minute longer and the heating restart is delayed.
Defrost is still reported on the minute it terminates · case 04
Every defrost is reported one minute longer and the heating restart is delayed.
Defrost is still reported on the minute it terminates · case 05
Every defrost is reported one minute longer and the heating restart is delayed.
Schedule lookup before the first event of the week uses the first event · case 01
Early Monday morning runs the Monday wake setpoint instead of Sunday night's sleep setpoint.
Schedule lookup before the first event of the week uses the first event · case 02
Early Monday morning runs the Monday wake setpoint instead of Sunday night's sleep setpoint.
Schedule lookup before the first event of the week uses the first event · case 03
Early Monday morning runs the Monday wake setpoint instead of Sunday night's sleep setpoint.
Schedule lookup before the first event of the week uses the first event · case 04
Early Monday morning runs the Monday wake setpoint instead of Sunday night's sleep setpoint.
Schedule lookup before the first event of the week uses the first event · case 05
Early Monday morning runs the Monday wake setpoint instead of Sunday night's sleep setpoint.
Schedule event does not apply at its own start minute · case 01
At exactly the programmed time the thermostat still shows the previous period.
Schedule event does not apply at its own start minute · case 02
At exactly the programmed time the thermostat still shows the previous period.
Schedule event does not apply at its own start minute · case 03
At exactly the programmed time the thermostat still shows the previous period.
Schedule event does not apply at its own start minute · case 04
At exactly the programmed time the thermostat still shows the previous period.
Schedule event does not apply at its own start minute · case 05
At exactly the programmed time the thermostat still shows the previous period.
Schedule lookup ignores the weekday of events · case 01
A weekend event overrides weekday times because only the minute of day is compared.
Schedule lookup ignores the weekday of events · case 02
A weekend event overrides weekday times because only the minute of day is compared.
Schedule lookup ignores the weekday of events · case 03
A weekend event overrides weekday times because only the minute of day is compared.
Schedule lookup ignores the weekday of events · case 04
A weekend event overrides weekday times because only the minute of day is compared.
Schedule lookup ignores the weekday of events · case 05
A weekend event overrides weekday times because only the minute of day is compared.
Schedule entries are scanned in the order they were entered · case 01
Editing an earlier period after a later one makes the lookup stop at the wrong event.
Schedule entries are scanned in the order they were entered · case 02
Editing an earlier period after a later one makes the lookup stop at the wrong event.
Schedule entries are scanned in the order they were entered · case 03
Editing an earlier period after a later one makes the lookup stop at the wrong event.
Schedule entries are scanned in the order they were entered · case 04
Editing an earlier period after a later one makes the lookup stop at the wrong event.
Schedule entries are scanned in the order they were entered · case 05
Editing an earlier period after a later one makes the lookup stop at the wrong event.
Permanent hold expires at the next schedule period while temporary hold persists · case 01
A "hold until next period" never ends, while a permanent hold is dropped at the next program change.
Permanent hold expires at the next schedule period while temporary hold persists · case 02
A "hold until next period" never ends, while a permanent hold is dropped at the next program change.
Permanent hold expires at the next schedule period while temporary hold persists · case 03
A "hold until next period" never ends, while a permanent hold is dropped at the next program change.
Permanent hold expires at the next schedule period while temporary hold persists · case 04
A "hold until next period" never ends, while a permanent hold is dropped at the next program change.
Permanent hold expires at the next schedule period while temporary hold persists · case 05
A "hold until next period" never ends, while a permanent hold is dropped at the next program change.
Temporary hold remembers the period of the first hold ever set · case 01
A temporary hold set in a later period expires immediately.
Temporary hold remembers the period of the first hold ever set · case 02
A temporary hold set in a later period expires immediately.
Temporary hold remembers the period of the first hold ever set · case 03
A temporary hold set in a later period expires immediately.
Temporary hold remembers the period of the first hold ever set · case 04
A temporary hold set in a later period expires immediately.
Temporary hold remembers the period of the first hold ever set · case 05
A temporary hold set in a later period expires immediately.
Hold setpoint accepts values outside the thermostat limits · case 01
A remote or keypad hold can command 40 F or 95 F.
Hold setpoint accepts values outside the thermostat limits · case 02
A remote or keypad hold can command 40 F or 95 F.
Hold setpoint accepts values outside the thermostat limits · case 03
A remote or keypad hold can command 40 F or 95 F.
Hold setpoint accepts values outside the thermostat limits · case 04
A remote or keypad hold can command 40 F or 95 F.
Hold setpoint accepts values outside the thermostat limits · case 05
A remote or keypad hold can command 40 F or 95 F.
A temporary hold set during a permanent hold becomes permanent · case 01
Pressing the arrows during a vacation hold makes the new setpoint stick past the next period.
A temporary hold set during a permanent hold becomes permanent · case 02
Pressing the arrows during a vacation hold makes the new setpoint stick past the next period.
A temporary hold set during a permanent hold becomes permanent · case 03
Pressing the arrows during a vacation hold makes the new setpoint stick past the next period.
A temporary hold set during a permanent hold becomes permanent · case 04
Pressing the arrows during a vacation hold makes the new setpoint stick past the next period.
A temporary hold set during a permanent hold becomes permanent · case 05
Pressing the arrows during a vacation hold makes the new setpoint stick past the next period.