FA-92495 / HVAC thermostat control / Member archive
Hold setpoint accepts values outside the thermostat limits · case 05
A remote or keypad hold can command 40 F or 95 F.
Case contract
Thermostat hold logic; samples are [schedule_period_id, scheduled_setpoint, action] where action is None, "resume", ["temp", sp] or ["perm", sp]. A hold setpoint is clamped to 50.0-90.0 F (500-900 tenths). A temporary hold lasts until the schedule period id changes from the one in which the hold was set; a permanent hold lasts until resume. A new hold of either kind replaces the current hold. Return the effective setpoint per sample.
Why this case matters
Residential and light-commercial thermostats make these decisions sample by sample; each defect changes equipment calls in a way that shows up as short cycling, comfort complaints or equipment stress.
One recorded failure
Sample boundary fixtureThis sample comes from the broken implementation of a controlled reproducer.
| Boundary fixture | Actual | Expected | Outcome |
|---|---|---|---|
| regression: scenario 14 | [700, 689, 824, 824, 944, 944, 944, 527, 867] | [700, 689, 824, 824, 900, 900, 900, 527, 867] | Failed |