FA-92413 / HVAC thermostat control / Member archive
Minimum on time is measured from the first ever start · case 03
After the first cycle the compressor may stop right after starting because its start time is stale.
Case contract
Compressor protection sampled per minute; calls is a list of [demand, safety_ok]. After power-up the compressor may not start before minute startup_delay. Once started it runs at least min_on minutes even if demand ends; after stopping it stays off at least min_off minutes. A safety fault stops it immediately regardless of minimum on time, and that stop also starts the minimum off time; it cannot start while the safety is faulted. Return the compressor state per minute.
Why this case matters
Residential and light-commercial thermostats make these decisions sample by sample; each defect changes equipment calls in a way that shows up as short cycling, comfort complaints or equipment stress.
One recorded failure
Sample boundary fixtureThis sample comes from the broken implementation of a controlled reproducer.
| Boundary fixture | Actual | Expected | Outcome |
|---|---|---|---|
| regression: scenario 11 | [false, true, true, false, false, false, false, true, false, false, false, false, true, false, false, false, false, true] | [false, true, true, false, false, false, false, true, true, false, false, false, false, false, false, false, false, true] | Failed |