FA-92763 / HVAC thermostat control / Member archive
Optimal start has no maximum lead time · case 03
After a very cold night the system starts recovering many hours before occupancy.
Case contract
Optimal start for a heating setback, sampled per minute from minute 0; rate is the recovery rate in tenths F per hour. While not recovering, required minutes = ceil(max(0, occ_sp - temp) * 60 / rate); recovery starts (and latches) when minutes left until occupancy <= required, but never more than 180 minutes early, and in any case at occupancy. Return the active setpoint per minute.
Why this case matters
Residential and light-commercial thermostats make these decisions sample by sample; each defect changes equipment calls in a way that shows up as short cycling, comfort complaints or equipment stress.
One recorded failure
Sample boundary fixtureThis sample comes from the broken implementation of a controlled reproducer.
| Boundary fixture | Actual | Expected | Outcome |
|---|---|---|---|
| regression: lead limit | [700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700, 700] | [600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 600, 700, 700, 700, 700, 700] | Failed |