Economizer ramp starts from the closed position · case 02
After occupancy begins the damper opens to less than minimum ventilation on the first economizer step.
Case contract
Rooftop economizer per sample; samples are [outdoor, return_air, cooling_call, mixed_air, occupied] in tenths F. Economizing is enabled when outdoor <= high_limit - 2.0 F and outdoor < return - diff, and disabled when outdoor > high_limit or outdoor >= return. Unoccupied: damper 0%. Occupied, enabled and cooling: if mixed air < mat_low the damper steps down 10% but not below min_pos, otherwise it steps up 20% from at least min_pos, capped at 100%. Otherwise the damper sits at min_pos. Return [enabled, damper%] per sample.
Why this case matters
Residential and light-commercial thermostats make these decisions sample by sample; each defect changes equipment calls in a way that shows up as short cycling, comfort complaints or equipment stress.
One recorded failure
Sample boundary fixtureThis sample comes from the broken implementation of a controlled reproducer.
| Boundary fixture | Actual | Expected | Outcome |
|---|---|---|---|
| regression: cold mixed air | [[true, 20], [true, 40], [true, 30], [true, 30], [true, 30], [true, 30]] | [[true, 50], [true, 70], [true, 60], [true, 50], [true, 40], [true, 30]] | Failed |