FA-92512 / HVAC thermostat control / Member archive

Celsius press moves a whole degree Celsius · case 02

Each arrow press in C mode jumps 1 C (1.8 F) instead of 0.5 C.

Member previewVariant 2 · 3 implementations · 8 checks per implementation

Case contract

Thermostat setpoint keypad. The setpoint is stored in tenths F. In C mode the display shows the stored value converted to C and rounded half up to 0.5 C; a press moves the displayed value by 0.5 C and stores exactly 320 + half_degrees*9 tenths F. In F mode the display rounds half up to whole F and a press moves the whole-degree value by 1 F. After each press the stored value is clamped to 45.0-90.0 F. Return [display, stored_tenths_F] per press.

Why this case matters

Residential and light-commercial thermostats make these decisions sample by sample; each defect changes equipment calls in a way that shows up as short cycling, comfort complaints or equipment stress.

One recorded failure

Sample boundary fixture

This sample comes from the broken implementation of a controlled reproducer.

Boundary fixtureActualExpectedOutcome
regression: celsius off-grid start[["32.0", 900], ["32.0", 900]][["21.5", 707], ["22.0", 716]]Failed