FA-92329 / PLC ladder logic scan cycles / Member archive
INT saturation direction follows the first operand · case 04
Multiplying two negative numbers saturates to -32768 instead of 32767.
Case contract
16-bit INT math rung followed by a later fault-clearing rung, one op per scan; ops is a list of [a, b, ADD|SUB|MUL, clear]. A result outside -32768..32767 sets the overflow bit V for that instruction and the overflow trap; the stored result is saturated to 32767/-32768 when clamp is set or wrapped as 16-bit two's complement otherwise. V is recomputed per instruction. The later rung clears the trap when clear is true; a trap still set at end of scan halts the processor. Return [result, V, trap] per scan, then "halted" and stop if faulted.
Why this case matters
Ladder programs are executed as repeated scans; each defect here changes what a rung, timer, counter or data-table instruction reports on a particular scan, which is how commissioning and field faults are actually observed.
One recorded failure
Sample boundary fixtureThis sample comes from the broken implementation of a controlled reproducer.
| Boundary fixture | Actual | Expected | Outcome |
|---|---|---|---|
| regression: scenario 31 | [[-32768, true, false], [23550, false, false], [32767, true, false], [32767, true, false]] | [[32767, true, false], [23550, false, false], [-32768, true, false], [32767, true, false]] | Failed |
MEMBER ARCHIVE
The complete case is available to members.
This record includes three runnable implementations, regression fixtures, execution results, and source hashes.
Member access is invitation-based. Sign in with your invited account to inspect the sources.