FA-92103 / PLC ladder logic scan cycles / Member archive
Sequencer reset writes the home word to the destination · case 03
Resetting the sequencer changes the machine outputs instead of only rewinding the position.
Case contract
Sequencer output (SQO). words is the sequencer file whose element 0 is the home step; position starts at 0. On each rising edge of enable the position advances; past the last element it wraps to 1 (not 0). Each advance writes dest = (dest AND NOT mask) OR (word AND mask) in 16 bits. A reset input returns position to 0 without writing dest and has priority over a coincident advance; the enable edge memory is always updated. steps is a list of [enable, reset]; return [position, dest] per scan.
Why this case matters
Ladder programs are executed as repeated scans; each defect here changes what a rung, timer, counter or data-table instruction reports on a particular scan, which is how commissioning and field faults are actually observed.
One recorded failure
Sample boundary fixtureThis sample comes from the broken implementation of a controlled reproducer.
| Boundary fixture | Actual | Expected | Outcome |
|---|---|---|---|
| regression: scenario 2 | [[1, 30504], [1, 30504], [1, 30504], [1, 30504], [1, 30504], [1, 30504], [1, 30504], [1, 30504], [0, 36741], [0, 36741], [0, 36741]] | [[1, 30504], [1, 30504], [1, 30504], [1, 30504], [1, 30504], [1, 30504], [1, 30504], [1, 30504], [0, 30504], [0, 30504], [0, 30504]] | Failed |