FA-92057 / PLC ladder logic scan cycles / Member archive

A trigger at the exact completion time is counted as a task overlap · case 02

Periodic tasks whose execution equals the period are skipped every other cycle and the overlap counter climbs.

Member previewVariant 2 · 3 implementations · 8 checks per implementation

Case contract

Periodic task triggered every period ms from t=0; exec_times[k] is how long the k-th triggered execution would take. A trigger arriving while the previous execution is still running (trigger time < completion time) is an overlap: it is counted and skipped, not queued; a trigger exactly at completion starts normally. An execution longer than watchdog raises a major fault at start + watchdog and scheduling stops. Return [start_times, overlap_count, fault_time or None].

Why this case matters

Ladder programs are executed as repeated scans; each defect here changes what a rung, timer, counter or data-table instruction reports on a particular scan, which is how commissioning and field faults are actually observed.

One recorded failure

Sample boundary fixture

This sample comes from the broken implementation of a controlled reproducer.

Boundary fixtureActualExpectedOutcome
regression: watchdog exceeded[[10], 1, 22][[0, 10], 0, 22]Failed