FA-92054 / PLC ladder logic scan cycles / Member archive
Non-retentive outputs survive a power cycle · case 04
An output coil that was on before the power loss is reported on after prescan, before its rung has been solved.
Case contract
Latch (OTL), unlatch (OTU) and non-retentive output (OTE) rungs executed in program order each scan. rungs is a list of [instr, bit, condition_tag]; the rung is true when the condition input is true, or, for condition S:FS, on the first scan after power-up. A scan item {"power_cycle": true} models a power cycle: prescan clears only OTE destination bits, OTL/OTU bits are retentive, and the next scan is a first scan; it also reports the post-prescan state. OTL sets and OTU clears its bit only when its rung is true; the later rung wins. Return the sorted true bits after each item.
Why this case matters
Ladder programs are executed as repeated scans; each defect here changes what a rung, timer, counter or data-table instruction reports on a particular scan, which is how commissioning and field faults are actually observed.
One recorded failure
Sample boundary fixtureThis sample comes from the broken implementation of a controlled reproducer.
| Boundary fixture | Actual | Expected | Outcome |
|---|---|---|---|
| regression: scenario 11 | [["B:1"], ["B:1"], ["B:0", "B:1"], ["B:0", "B:1"], ["B:0", "B:1"], ["B:1"]] | [["B:1"], ["B:1"], ["B:0", "B:1"], ["B:1"], ["B:1"], ["B:1"]] | Failed |
MEMBER ARCHIVE
The complete case is available to members.
This record includes three runnable implementations, regression fixtures, execution results, and source hashes.
Member access is invitation-based. Sign in with your invited account to inspect the sources.